【发布时间】:2021-06-22 04:04:01
【问题描述】:
from pymodbus.payload import BinaryPayloadDecoder
from pymodbus.constants import Endian
from pymodbus.client.sync import ModbusTcpClient
def convertINT32(data):
decoder = BinaryPayloadDecoder.fromRegisters(data, Endian.Big, wordorder=Endian.Little)
return decoder.decode_32bit_int()
client = ModbusTcpClient(host="176.219.182.106", port="502")
client.connect()
data = client.read_holding_registers(address=230,count=10,unit=1)
eaPlus = convertINT32(data.registers[0:2]) # kWh Del
eaNeg = convertINT32(data.registers[2:4]) # kWh Rec
erPlus = convertINT32(data.registers[4:6]) #VARh Del
erNeg = convertINT32(data.registers[6:8]) #kVAR Rec
client.close()
print("Active Energy Plus: %s \nActive Energy Negative: %s \nReactive Energy Plus: %s \nReactive Energy Negative: %s" %(eaPlus,eaNeg, erPlus, erNeg))
print("----------------------------")
print("Register List: %s" % data.registers)
print("----------------------------")
print("Actual values are APPROXİMATE:\nActive Energy Plus: 989 \nActive Energy Negative: 3879077 \nReactive Energy Plus: 268384 \nReactive Energy Negative: 361")
我正在尝试从 Schneider ION7650 读取仪表值(如果你不知道我没关系),这里是一个 modbus 寄存器列表:
我知道确切的值,并将结果与它们进行比较,我的代码看起来像是错误的。 IP 地址和端口是可访问的,因此您可以访问仪表。这里有什么问题?
然后输出:
Active Energy Plus: 3867613
Active Energy Negative: 275048
Reactive Energy Plus: 6270
Reactive Energy Negative: 3866985
----------------------------
Register List: [989, 59, 12904, 4, 6270, 0, 361, 59, 23532, 65535]
----------------------------
Actual values are APPROXİMATE:
Active Energy Plus: 989
Active Energy Negative: 3879077
Reactive Energy Plus: 268384
Reactive Energy Negative: 361
您还可以检查来自here 的实时值,然后单击消耗
【问题讨论】:
标签: python modbus-tcp pymodbus