【问题标题】:Pymodbus Registers Can Not Decode CorrectlyPymodbus 寄存器无法正确解码
【发布时间】:2021-06-22 04:04:01
【问题描述】:
from pymodbus.payload import BinaryPayloadDecoder
from pymodbus.constants import Endian
from pymodbus.client.sync import ModbusTcpClient

def convertINT32(data):
       decoder = BinaryPayloadDecoder.fromRegisters(data, Endian.Big, wordorder=Endian.Little)
       return decoder.decode_32bit_int()

client = ModbusTcpClient(host="176.219.182.106", port="502")
client.connect()
data = client.read_holding_registers(address=230,count=10,unit=1)

eaPlus = convertINT32(data.registers[0:2]) # kWh Del
eaNeg = convertINT32(data.registers[2:4])  # kWh Rec
erPlus = convertINT32(data.registers[4:6]) #VARh Del
erNeg = convertINT32(data.registers[6:8])  #kVAR Rec

client.close()

print("Active Energy Plus: %s \nActive Energy Negative: %s \nReactive Energy Plus: %s \nReactive Energy Negative: %s" %(eaPlus,eaNeg, erPlus, erNeg))
print("----------------------------")
print("Register List: %s" % data.registers)
print("----------------------------")
print("Actual values are APPROXİMATE:\nActive Energy Plus: 989 \nActive Energy Negative: 3879077 \nReactive Energy Plus: 268384 \nReactive Energy Negative: 361")

我正在尝试从 Schneider ION7650 读取仪表值(如果你不知道我没关系),这里是一个 modbus 寄存器列表:

我知道确切的值,并将结果与​​它们进行比较,我的代码看起来像是错误的。 IP 地址和端口是可访问的,因此您可以访问仪表。这里有什么问题?

然后输出:

Active Energy Plus: 3867613 
Active Energy Negative: 275048
Reactive Energy Plus: 6270
Reactive Energy Negative: 3866985
----------------------------
Register List: [989, 59, 12904, 4, 6270, 0, 361, 59, 23532, 65535]
----------------------------
Actual values are APPROXİMATE:
Active Energy Plus: 989
Active Energy Negative: 3879077
Reactive Energy Plus: 268384
Reactive Energy Negative: 361

您还可以检查来自here 的实时值,然后单击消耗

【问题讨论】:

    标签: python modbus-tcp pymodbus


    【解决方案1】:

    我找到了解决办法。当我从 BinaryDecoder.fromregisters 中删除 wordorderer 时。我还在 Modbus Poll 中看到了订单列表。有很多选择,比如

    • A B C D(字节顺序:Big Endian)
    • D C B A
    • C D A B
    • B A D C(字节顺序:Little Endian)

    如果我错了,请纠正我。如何阅读其他选项。还有什么是词序?是否有任何组合读取“C D A B 组合,如 wordorder=Endian.Big byteorder=Endian.Little

    【讨论】:

      【解决方案2】:

      来自Modbus Protocol and Register Map for ION Devices documentation(第12页):

      根据 Modbus 协议,为了响应对特定从设备的寄存器 4xxxx 的请求,Modbus 主设备从从设备读取寄存器 xxxx-1。例如,寄存器 40011 对应保持寄存器 10。

      因此将 address 设置为 229 而不是 230 以读取从地址 230 开始的 10 个寄存器。此外,字节序和字序都是大端序。

      我试过了,得到了预期的值。

      【讨论】: